DIAGNOSIS FOR CAUSES OF FOULING FORMATION IN DIRECT DISCHARGING TYPE COOLING WATER SYSTEM
The fouling deposition on surface of the heat exchanger can tremendously reduce the heat transfer efficiency of said exchanger
hence
it is very important to diagnose the causes of fouling formation.Combined with the actual example in one power plant
many analyses
such as water quality analysis
ignition analysis
plasma transmitted spectrum
and scanning electron microscopy etc.
have been carried out
to analyse the quality of cooling water
and properties in aspects of fouling
silt
and microorganism respectively.The results show that the silt carried in cooling water of the said plant is the main cause of fouling formation on the surface of heat exchanger in cooling water system.Hence
it is recommended as in the foollowing:(1) the silt should be regarded as a special item in daily quality monitoring process of the direct discharging type cooling water system;(2) the cooling water intake port should be kept enough distance from the bottom of water supply reservoir.