CAUSE ANALYSIS AND PREVENTION OF ROOF TYPE SUPERHEATER LEAKAGE FOR BOILERS[J]. Thermal power generation, 2005, (11).
DOI:
CAUSE ANALYSIS AND PREVENTION OF ROOF TYPE SUPERHEATER LEAKAGE FOR BOILERS[J]. Thermal power generation, 2005, (11). DOI: 10.19666/j.rlfd.2005.11.029.
CAUSE ANALYSIS AND PREVENTION OF ROOF TYPE SUPERHEATER LEAKAGE FOR BOILERS
摘要
对中国铝业中州分公司锅炉顶棚过热器管泄漏进行了分析
认为炉水品质差、炉水中含有大量的溶解氧
以及汽水分离效果不好、机械携带严重等是造成泄漏的主要原因。对此
提出了停用第二氧化铝厂的蒸发回水
改善除氧器运行条件等措施。实施后
锅炉顶棚管的腐蚀泄漏得到了有效遏制。
Abstract
The roof type superheater leakage of boilers in Zhongzhou Branch Company under Sinoaluminium Industry has been analysed. It is believed that the main factors resulting in said leakage are as follows: bad quality of the boiler water
large amount of dissolved oxygen in boiler water
as well as bad effectiveness of steamwater separation
and serious mechanical carryover etc.. For these
prevention measures
such as stopping utilization of evaporation back water from The Alumiuium Oxide Factory No 2
and improving operation conditions of the deaerator etc.
have been put forward. After implementation
leakages resulted from the roof tube corrosion of boilers have been effectively avoided.