ANALYSIS OF MULTIPLE-UNIT VENTILATING AND COOLINGDOWN FOR MAIN BUILDING IN THERMAL POWER PLANT BY USING AIR COOLERS
Study on mutiple-unit ventilating flow field of main building (turbine hall) in thermal power plant adopting air coolers has been carried out by using computational fluid dymamics. Results show that the natural ventilation of the main building was destroyed in the case of air cooler being 12m apart from the mzin building
ventilating and cooling all do not satisfy the requirements of specifications
and mechanical ventilation has to be asisted. Results of calculation indicate that the multiple-unit ventilation made of combining natural inlet air with mechnical exhaust air
or combining mechanical inlet air with natural exhaust air
can be used for the main building respe-tively
to satisfy the requirements of ventilating and coolingdown specified in design.