CAUSE ANALYSIS OF POLIUTION IN FIRERESISTANT OIL SYSTEM FOR 900MW NUCLEAR POWERGENERATING UNIT[J]. Thermal power generation, 2004, (5): 66-67.
DOI:
CAUSE ANALYSIS OF POLIUTION IN FIRERESISTANT OIL SYSTEM FOR 900MW NUCLEAR POWERGENERATING UNIT[J]. Thermal power generation, 2004, (5): 66-67. DOI: 10.19666/j.rlfd.2004.05.021.
CAUSE ANALYSIS OF POLIUTION IN FIRERESISTANT OIL SYSTEM FOR 900MW NUCLEAR POWERGENERATING UNIT
Directing against the problems of frequently alarming from the strainer
as well as quantity and frequency of replacing the cartriges in excess normality
an analysis of inspecting the fireresistant oil system has been carried out
including: (1) evaluation of the quality for fireresistant oil; (2) analysis of pollutants on the cartriges;(3) analysis of dark schistous matters on the cartriges; (4) investigation of local overheat points in the fireresistant oil system. After finding out the composition and source of pollutants in the fireresistant system