STUDY ON OVER-TEMPERATURE OF PLATEN TYPE REHEATER FOR BOILERS WITH FOUR CORNER TANGENTIAL FIRING[J]. Thermal power generation, 2003, (10): 38-40.
DOI:
STUDY ON OVER-TEMPERATURE OF PLATEN TYPE REHEATER FOR BOILERS WITH FOUR CORNER TANGENTIAL FIRING[J]. Thermal power generation, 2003, (10): 38-40. DOI: 10.19666/j.rlfd.2003.10.012.
STUDY ON OVER-TEMPERATURE OF PLATEN TYPE REHEATER FOR BOILERS WITH FOUR CORNER TANGENTIAL FIRING
摘要
通过试验得到屏式再热器的壁温分布
分析试验结果找出超温的再热器管。结合锅炉炉膛出口水平烟道的烟温分布
认为超温主要为水平烟道烟温偏差所致
对此提出了更换材质、加大三次风的反切角度、增加FF层二次风的反切等改进和运行调整措施
Abstract
Through tests
the wall temperature distribution of platen type reheater has been obtained
and the over-temperature of reheater tube being known from the analysis of test results. Combined with the flue gas temperature distribution of outlet horizontal gas duct from the furnace of boiler
it is considered that the cause resulting in over-temperature is mainly due to temperature deviation in the horizontal flue gas duct
and the correspanding retrofit of equipments and operational adjustment being put forward.
Numerical study on combustion characteristics of a tangentially fired pulverized-coal boiler in O2/CO2 atmosphere
AN APPROACH TO HIGH EFFECTIVE COMBUSTION TECHNOLOGY FOR LOW NOx EMISSION ON 1025t/h BOILER IN XIANGTAN POWER PLANT
APPLICATION OF FOUR CORNER OPPOSED TANGENTIAL FIRING ON UTILITY BOILERS
TESTING STUDY AND COMPREHESIVE WAY TO CONTROL SLAGGING IN THE FURNACE AND OVERTEMPERATURE OF THE SUPERHEATER FOR BOILER No.8 IN BAOTOU THERMAL POWER PLANT No.1
NEW CALCULATION SOFTWARE AND ITS PRACTICAL APPLICATION FOR CALCULATING WALL TEMPERATURE OF HIGH TEMPERATURE CONVECTIVE HEATING SURFACE FOR A BOILER