RETROFIT OF TWO 130t/h PULVERIZED COAL BOILERS IN YILI THERMAL POWER PLANT NO.2 DUE TO HIGH EXHAUST GAS TEMPERATURE THEREOF[J]. Thermal power generation, 2003, (9): 34-35.
DOI:
RETROFIT OF TWO 130t/h PULVERIZED COAL BOILERS IN YILI THERMAL POWER PLANT NO.2 DUE TO HIGH EXHAUST GAS TEMPERATURE THEREOF[J]. Thermal power generation, 2003, (9): 34-35. DOI: 10.19666/j.rlfd.2003.09.011.
RETROFIT OF TWO 130t/h PULVERIZED COAL BOILERS IN YILI THERMAL POWER PLANT NO.2 DUE TO HIGH EXHAUST GAS TEMPERATURE THEREOF
In view of troublesome problems of high exhaust gas temperature and high hot air temperature having existed after putting two CG-130/3.82-M12 type boilers into operation at Yili Thermal Power Plant NO.2
corresponding retrofitting schemes have been studied and worked out
namely renewing 107m 2 area of superheater in the boiler
increasing heating surface area of a party of the economizer
adding 8 steam soot-blowers in the heat recovery gas duct. The operation after retrofitting shows
the exhaust gas temperature having been lowered by 30℃