SOME MEASURES TAKEN TO IMPROVE THE RELIABILITY OF TEMPERATURE PROTECTION ON TURBINE-GENERATOR SETS AT MAWAN POWER PLANT[J]. Thermal power generation, 2002, (1): 59-60.
DOI:
SOME MEASURES TAKEN TO IMPROVE THE RELIABILITY OF TEMPERATURE PROTECTION ON TURBINE-GENERATOR SETS AT MAWAN POWER PLANT[J]. Thermal power generation, 2002, (1): 59-60. DOI: 10.19666/j.rlfd.2002.01.024.
SOME MEASURES TAKEN TO IMPROVE THE RELIABILITY OF TEMPERATURE PROTECTION ON TURBINE-GENERATOR SETS AT MAWAN POWER PLANT
摘要
通过对妈湾电厂汽轮发电机历年温度保护误动的原因分析
采取增加温度测点、增加适当延时、增加温度变化率和机组负荷辅助判据等有效措施
确保了汽轮发电机温度保护在不发生拒动的基础上
尽可能减少误动。
Abstract
Through cause analysis for malfunctions of temperature protection occurred in recent years on turbine-generator sets at Mawan Power Plant
some effective measures
such as to increase the temperature-measuring points
expand appropriate time delay
add temperature variation ratio and load of generating sets as subsidiary criteria
was taken
ensuring the malfunction of said protection may be decreased as considerably as possible on the basis of non-occurrence of miss operation.