CAUSE ANALYSIS ON DISTRIBUTED FROST-CRACKS OF FIN-TUBE BANDLES IN HAILER TYPE AIR-COOLED SYSTEM
摘要
对海勒式空冷系统翅片管束分散型冻坏成因进行分析
认为冬季冷却柱排水时使排空区产生压力
形成负压
导致循环冷却水汽化
随后汽化的冷却水又凝结并形成冰瘤
以致堵塞管束引发铝管冻裂
对此提出了预防冰瘤堵塞的技术措施。
Abstract
The title events have been analyzed. It is considered that the presure drop in the empty space would be generated while the water in the cooling column had been discharged in winter season
and the negative pressure established in the column would have been resulting in evaporation of circulating cooling water. Then
the evaporated cooling water would be condensed again
forming ice-tumours in fin-tubes with the result that tube-bandles would be blocked up
causing frost-cracks of aluminum tubes. In this paper some technical measures are recommended for preventing blockage by ice-tumours.