RUPTURE ANALYSIS OF A STEAM LEAD FROM A HTSH TEMPERATURE SUPERHEATER ON A FOSSIL POWER STATION[J]. Thermal power generation, 1993, (4): 28-33.
DOI:
RUPTURE ANALYSIS OF A STEAM LEAD FROM A HTSH TEMPERATURE SUPERHEATER ON A FOSSIL POWER STATION[J]. Thermal power generation, 1993, (4): 28-33. DOI: 10.19666/j.rlfd.1993.04.006.
RUPTURE ANALYSIS OF A STEAM LEAD FROM A HTSH TEMPERATURE SUPERHEATER ON A FOSSIL POWER STATION
This paper presents a study on the rup(?)re of a steam lead elbow used in a EII-670/140 model boiler. The macrofractography and mic(?)structure examinations were used to analyse the problem. It was found that the rupture was of brittle fracture character
which was attributed to the accumulated creep damage under the high stress and tempereature.