陶瑞祥, 王成珠, 姜云土, et al. Analysis on Electric Field of Stress Cone with XLPE Insulation Shrinkage of 220 kV Cable Intermediate Joints[J]. 2021, 40(11): 23-28.
DOI:
陶瑞祥, 王成珠, 姜云土, et al. Analysis on Electric Field of Stress Cone with XLPE Insulation Shrinkage of 220 kV Cable Intermediate Joints[J]. 2021, 40(11): 23-28. DOI: 10.19585/j.zjdl.202111004.
Analysis on Electric Field of Stress Cone with XLPE Insulation Shrinkage of 220 kV Cable Intermediate Joints
cable joint with unilateral XLPE insulation shrinkage and cable joint with bilateral XLPE insulation shrinkage as the objects of study
the paper calculates electric field distributions inside the cable joints and studies electric field change on specific paths in case of XLPE insulation shrinkage without separating from stress cones. Moreover
it pays special attention to electric field change at the stress cone terminals that are prone to breakdown in practical operation. The calculation results show that there are maximum electric fields at stress cone terminals of both normal cable joints and deficient joints with XLPE insulation shrinkage; moreover
in the case of XLPE insulation shrinkage the electric field at stress cone terminal increases evidently
and when the XLPE insulation of the cable joint shrinks
the electric field of the contact section between the high-voltage stress cone and XLPE increases with the shrinkage expansion.However
the effect of the shrinkage distance on the end of the high-voltage stress cone is not significant. Air gaps produced by XLPE shrinkage wield more influence on the stress cones than XLPE insulation shrinkage does. In the case of bilateral XLPE insulation shrinkage or air gaps produced by the shrinkage
the electric field distributions in key areas on both sides do not interact. The research findings can provide theoretical support to cable joint fault diagnosis.