Tao Jiang, Nan Ye, Xue Li, et al. Multi-Synchrosqueezing Transform Approach for Forced Oscillation Source Location of Power Systems in Time-Frequency and Frequency Domains[J]. CSEE Journal of Power and Energy Systems, 2026, 12(3): 1180-1193.
DOI:
Tao Jiang, Nan Ye, Xue Li, et al. Multi-Synchrosqueezing Transform Approach for Forced Oscillation Source Location of Power Systems in Time-Frequency and Frequency Domains[J]. CSEE Journal of Power and Energy Systems, 2026, 12(3): 1180-1193. DOI: 10.17775/CSEEJPES.2025.04990.
Multi-Synchrosqueezing Transform Approach for Forced Oscillation Source Location of Power Systems in Time-Frequency and Frequency Domains
摘要
Abstract
Forced oscillation (FO) has posed a significant threat to the power system stability. Accurate and fast FO source location (FOSL) plays an essential role in mitigating FOs. However
most existing FOSL methods fail in dealing with non-stationary FOs and exciter-induced FOs. To overcome the above issues
a multi-synchrosqueezing transform (MSST)-based data-driven approach is developed in this paper to locate the FO source in bulk power systems by using measurement data. Firstly
MSST matrices of multi-channel measurements are formed by MSST. Then
the bus time-frequency representation (BTFR) defined and calculated from the MSST matrices is employed to extract the multi-channel FO components via the ridge detection technology. Furthermore
the MSST-based dissipating energy flow (DEF) model in the time-frequency domain and the dissipating energy spectrum (DES) model in the frequency domain are derived from the conventional time-domain DEF model
and their corresponding FOSL criteria are established. Moreover
an auxiliary criterion of the proposed approach has been developed to overcome the malfunction of the conventional DEF in interactions between generators. The performance of the proposed FOSL method is evaluated with simulation data from the WECC 240-bus and WECC 179-bus test systems
as well as field measurements from ISO New England. The results demonstrate the efficiency and accuracy of the proposed method in locating FO sources.