Jinglei Deng, Liangzhong Yao, Jian Xu, et al. Faulted Feeder Selection Based on Active Harmonic Injection of CIDGs for Small Current Grounding System[J]. CSEE Journal of Power and Energy Systems, 2026, 12(3): 1234-1251.
DOI:
Jinglei Deng, Liangzhong Yao, Jian Xu, et al. Faulted Feeder Selection Based on Active Harmonic Injection of CIDGs for Small Current Grounding System[J]. CSEE Journal of Power and Energy Systems, 2026, 12(3): 1234-1251. DOI: 10.17775/CSEEJPES.2024.07690.
Faulted Feeder Selection Based on Active Harmonic Injection of CIDGs for Small Current Grounding System
摘要
Abstract
When a single-line grounding (SLG) fault occurs in a small current grounding system (SCGS)
the weak fault characteristics pose a challenge to the fault line selection (FFS). To improve the reliability of FFS
a new FFS method based on harmonic active injection of converter interfaced distributed generator (CIDG) is proposed in the paper. First
by analyzing the distribution law and attenuation characteristics of the harmonic current actively injected by CIDG in the system
the active injection characteristic harmonic current signal that can meet the needs of FFS is selected
and then
a characteristic harmonic current signal injection method based on CIDG active control is designed. On this basis
an FFS method based on the amplitude-phase relationship of harmonic current is proposed
enabling the method to simultaneously meet the requirements of fault line selection and phase selection requirements. PSCAD/EMTDC simulation analysis verifies the effectiveness and superiority of the proposed method compared to existing methods.