Weijie Wen, Rui Lyu, Botong Li, et al. Analysis and Experimental Study of an Improved Two-Level Voltage-Source Converter with DC Fault Ride-Through Capability[J]. CSEE Journal of Power and Energy Systems, 2026, 12(3): 1400-1410.
DOI:
Weijie Wen, Rui Lyu, Botong Li, et al. Analysis and Experimental Study of an Improved Two-Level Voltage-Source Converter with DC Fault Ride-Through Capability[J]. CSEE Journal of Power and Energy Systems, 2026, 12(3): 1400-1410. DOI: 10.17775/CSEEJPES.2023.04890.
Analysis and Experimental Study of an Improved Two-Level Voltage-Source Converter with DC Fault Ride-Through Capability
摘要
Abstract
The two-level voltage-source converter (2L VSC) is the key equipment in a microgrid. However
power electronic devices in VSC are vulnerable to surge current under DC faults. Up to now
existing methods to deal with DC faults cannot balance fault current elimination performance and investment. To solve this problem
by adding a unit with a thyristor anti-parallel with a diode in the up-or down-bridge-arm of each phase
an improved 2L VSC with DC fault ride-through capability is proposed in this paper. The topology and working principle of the improved VSC are presented. The parameter design method of the proposed 2L VSC is discussed in terms of current and voltage requirements during DC fault ride-through. The simulation and experiments are carried out for verification
and the results are consistent with the theoretical analysis
showing that the fault current inside the proposed VSC could be eliminated within 1ms
and there are no overcurrent or overvoltage issues. In the end
comparisons between the proposed method and the existing methods are presented to prove the superiority of the proposed 2L VSC.