Shuyan Wang, Shiyun Xu, Huadong Sun, et al. Quantification Method for Maximum Access Capacity of Renewable Energy in Multi-Infeed System with Temporary Overvoltage Constraints[J]. CSEE Journal of Power and Energy Systems, 2026, 12(3): 1364-1373.
DOI:
Shuyan Wang, Shiyun Xu, Huadong Sun, et al. Quantification Method for Maximum Access Capacity of Renewable Energy in Multi-Infeed System with Temporary Overvoltage Constraints[J]. CSEE Journal of Power and Energy Systems, 2026, 12(3): 1364-1373. DOI: 10.17775/CSEEJPES.2023.03710.
Quantification Method for Maximum Access Capacity of Renewable Energy in Multi-Infeed System with Temporary Overvoltage Constraints
摘要
Abstract
After a fault disturbance
there is a risk of temporary overvoltage in areas where renewable energy is aggregated
which can lead to the disconnection of renewable energy and threaten the safe and stable operation of the power grid. The capacity of input access to a multi-input system affects the temporary overvoltage level. Therefore
there exists a maximum access capacity that prevents the renewable energy from disconnecting from the grid in the event of a fault disturbance. To solve for the maximum access capacity
this paper first analyzes the reasons for the temporary overvoltage in the renewable energy AC transmission system caused by the fault disturbance
according to the renewable energy low voltage ride through (LVRT) control strategy. Then
a mathematical model for solving the temporary overvoltage maximum value in such a system with multiple inputs is presented. On top of that
an optimization model for the maximum access capacity of renewable energy
which is subject to the constraint of overvoltage safety
is established. The optimization model is solved using the tracking center trajectory interior point method to obtain the maximum access capacity of the multiple-input system and the optimal output distribution of each renewable energy source. Further
the cosine similarity is used to evaluate which output distribution is better for the same access capacity. Finally
the effectiveness of the proposed method for quantifying the maximum access capacity of multi-feeder systems is verified in a practical engineering example.
关键词
Keywords
references
2. International Energy Agency, “ World Energy Outlook 2022 ,” IEA Publications, Paris, France, Nov. 2022. [Online ] . Available: https://www.iea.org/reports/world-energy-outlook-2022.
8. North American Electric Reliability Corporation and Texas Reliability Entity, “Panhandle Wind Disturbance: Texas Event: March 22, 2022,” Joint NERC and Texas RE Staff Report , North American Electric Reliability Corporation, Atlanta, GA, USA, Aug. 2022. [Online ] . Available: https://www.nerc.com/globalassets/our-work/reports/event-reports/panhandle_wind_disturbance_report.pdf.
9. North American Electric Reliability Corporation and Texas Reliability Entity, “Odessa Disturbance: Texas Events: May 9, 2021 and June 26, 2021,” Joint NERC and Texas RE Staff Report , North American Electric Reliability Corporation, Atlanta, GA, USA, Sep. 2021. [Online ] . Available: https://www.nerc.com/globalassets/our-work/reports/event-reports/odessa_disturbance_report.pdf.