Hanhang Yin, Xiaoping Zhou, Lerong Hong, et al. Successive Commutation Failure Mechanism Analysis and Prevention of Multi-infeed HVDC System Considering Reactive Power and Harmonic Interaction[J]. CSEE Journal of Power and Energy Systems, 2026, 12(5): 2425-2439.
DOI:
Hanhang Yin, Xiaoping Zhou, Lerong Hong, et al. Successive Commutation Failure Mechanism Analysis and Prevention of Multi-infeed HVDC System Considering Reactive Power and Harmonic Interaction[J]. CSEE Journal of Power and Energy Systems, 2026, 12(5): 2425-2439.DOI: 10.17775/CSEEJPES.2022.08200.
Successive Commutation Failure Mechanism Analysis and Prevention of Multi-infeed HVDC System Considering Reactive Power and Harmonic Interaction
摘要
Abstract
This paper studies the successive commutation failure (SCF) mechanism considering the reactive power and harmonic interaction of a multi-infeed high voltage direct current (MIDC) system. It was found that the increase of reactive power exchanged on the tie line led to a decrease in the AC voltage amplitude of the healthy line during the SCF development stage. Hence
the probability of SCF increases due to the reactive power interaction. Besides
the voltage distortion components in AC voltage of healthy lines caused by harmonic interaction play a negative role in the commutation process
which may lead to SCF. Also
there is a nonlinear coupling between the effects of reactive power and harmonics on SCF. Thus
the reactive power impact index (RPII) and the voltage distortion index (VDI) are proposed to assess the degree of reactive power impact and voltage distortion of the DC line
respectively. Furthermore
the SCF prevention strategy of the MIDC system is proposed
which is realized by reducing the advance angle of the faulty line based on RPII and triggering the healthy line earlier based on VDI. Finally
the simulation models of the MIDC CIGRE benchmark system and Henan multi-infeed UHVDC system are built
and the effectiveness of the proposed SCF prevention strategy is verified under different fault types.