Jiale Wu, Yangzhi Gong, Peiqi Xiong, et al. Synergistic Promotion of Electrical, Mechanical and Thermal Properties for Silicone Rubber-based Field Grading Material via Compound Modification[J]. CSEE Journal of Power and Energy Systems, 2024, 10(1): 337-350.
DOI:
Jiale Wu, Yangzhi Gong, Peiqi Xiong, et al. Synergistic Promotion of Electrical, Mechanical and Thermal Properties for Silicone Rubber-based Field Grading Material via Compound Modification[J]. CSEE Journal of Power and Energy Systems, 2024, 10(1): 337-350.DOI: 10.17775/CSEEJPES.2022.02190.
Synergistic Promotion of Electrical, Mechanical and Thermal Properties for Silicone Rubber-based Field Grading Material via Compound Modification
摘要
Abstract
Use of nonlinear conductive SiC/silicone rubber (SR) field grading material (FGM) can improve the local field concentration of composite insulators. Adding large volume fraction and large-size SiC particles (SiCp) into SR can obtain a good field grading effect
but it is accompanied by the deterioration of mechanical properties. Compounding SiC with different shapes can solve this contradiction. By incorporating one-dimensional SiC whiskers (SiCw) to synergize with granular SiCp
SiC/SR FGM with better field-dependent conductivity
mechanical properties and thermal conductivity than large-size SiCp and large volume fraction filling case can be obtained by using smaller size SiCp and lower filling contents. The simulations of 500 k V line insulators show that the modified SiC/SR FGM can reduce the maximum field strength along the insulator surface and at sheath-core rod interfaces by 55% and 71.4%
respectively. The combined application of FGM and grading ring can achieve a complementary effect. Using FGM to partially replace the role of the grading rings
the field strength indicators can still meet the operational requirements after the tube radius and shielding depth of the grading rings at both ends are reduced by 36.2% and 40% separately
which is a benefit to alleviating the problems of high weight and large volume faced by traditional field grading methods.
Filler Size Effect on Tuning Electrical, Mechanical, and Thermal Properties of Field Grading Composites
Metal particle contamination in gas-insulated switchgears/gas-insulated transmission lines
Electrical Tracking, Erosion and Fire Retardancy Performance of Silicone Rubber Insulation Containing Aluminum Trihydrate, Graphene and Glass Fiber Additives
Risk assessment and management of electricity markets: A review with suggestions
Frequency control at the power sending side for HVDC asynchronous interconnections between yunnan power grid and the rest of CSG
Related Author
Xiaolei Zhao
Jun Hu
Xiao Yang
Zhiwen Huang
Xingming Bian
Yuanbao Lin
Jinliang He
Jian Wang
Related Institution
Department of Electrical Engineering, State Key Laboratory of Power Systems, Tsinghua University
North China Electric Power University, School of Electrical and Electronic Engineering
Key Laboratory of Control of Power Transmission and Conversion, Ministry of Education, Shanghai Jiao Tong University
Department of Chemistry, University of Oxford
State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University