Hong Shen, Zhonghao Dongye, Lei Qi, et al. Modeling of High-frequency Electromagnetic Oscillation for DC Fault in MMC-HVDC Systems[J]. CSEE Journal of Power and Energy Systems, 2023, 9(3): 1151-1160.
DOI:
Hong Shen, Zhonghao Dongye, Lei Qi, et al. Modeling of High-frequency Electromagnetic Oscillation for DC Fault in MMC-HVDC Systems[J]. CSEE Journal of Power and Energy Systems, 2023, 9(3): 1151-1160.DOI: 10.17775/CSEEJPES.2021.06370.
Modeling of High-frequency Electromagnetic Oscillation for DC Fault in MMC-HVDC Systems
摘要
Abstract
DC short-circuit faults pose a hazard to the operation of a modular multilevel converter (MMC)-based high voltage direct current (HVDC) system
necessitating reliable fault clearing solutions with rapid reaction. However
because the parasitic capacitances of the main equipment oscillate with the lumped inductances of the HVDC system
strong electromagnetic oscillations with multiple frequencies occur during clearance transients. These oscillations will disturb the HVDC system's protection and control systems. Therefore
this paper focuses on the modeling of these oscillations. First
an equivalent circuit for the MMC-based HVDC system is proposed
taking into account the parasitic capacitances of the system's major components
such as DC reactors
connecting cables
and DC circuit breakers (DCCBs). Second
four distinct oscillation stages are postulated based on action coordination of MMCs and DCCBs
and the associated analytical equations for the oscillation frequencies are derived. Third
a 200 kV MMC-based DC converter station is subjected to an 6ms/6kA pole-to-pole (PTP) short-circuit test. Electromagnetic oscillations have a frequency range of several kHz to several hundreds of kHz. The measured waveforms correspond well with simulated results
including the parasitic characteristics. Additionally
the relative errors between the simulated and measured frequencies are less than 5%.