Successive MISOCP Algorithm for Islanded Distribution Networks with Soft Open Points
Regular Papers|更新时间:2026-10-15
|
Successive MISOCP Algorithm for Islanded Distribution Networks with Soft Open Points
CSEE Journal of Power and Energy SystemsVol. 9, Issue 1, Pages: 209-220(2023)
作者机构:
1. Key Laboratory of Smart Grid of Ministry of Education, Key Laboratory of Smart Energy & Information Technology of Tianjin Municipality, Tianjin University,Tianjin,China
2. China Electric Power Research Institute,Beijing,China
Tao Zhang, Yunfei Mu, Hongjie Jia, et al. Successive MISOCP Algorithm for Islanded Distribution Networks with Soft Open Points[J]. CSEE Journal of Power and Energy Systems, 2023, 9(1): 209-220.
DOI:
Tao Zhang, Yunfei Mu, Hongjie Jia, et al. Successive MISOCP Algorithm for Islanded Distribution Networks with Soft Open Points[J]. CSEE Journal of Power and Energy Systems, 2023, 9(1): 209-220.DOI: 10.17775/CSEEJPES.2021.02910.
Successive MISOCP Algorithm for Islanded Distribution Networks with Soft Open Points
An optimal operation scheme is of great significance in islanded distribution networks to restore critical loads and has recently attracted considerable attention. In this paper
an optimal power flow (OPF) model for islanded distribution networks equipped with soft open points (SOPs) is proposed. Unlike in the grid-connected mode
the adequacy of local power generation in distribution networks is critical for islanded systems. The proposed approach utilizes the power output of local distributed generations (DGs) and the benefits of reactive power compensation provided by SOPs to allow maximum loadability. To exploit the available resources
an optimal secondary droop control strategy is introduced for the islanded distribution networks
thereby minimizing load shedding. The formulated OPF problem is essentially a mixed-integer nonlinear programming (MINLP) model. To guarantee the computation efficiency and accuracy. A successive mixed-integer second-order cone programming (S-MISOCP) algorithm is proposed for handling the nonlinear islanded power flow formulations. Two case studies
incorporating a modified IEEE 33-bus system and IEEE 123-bus system
are performed to test the effectiveness of the proposed approach.