Zakiud Din, Jianzhong Zhang, Zheng Xu, et al. Impact of Dead-Time on Resonance in Doubly Fed Induction Generator Under Weak Grid[J]. CSEE Journal of Power and Energy Systems, 2025, 11(3): 1070-1079.
DOI:
Zakiud Din, Jianzhong Zhang, Zheng Xu, et al. Impact of Dead-Time on Resonance in Doubly Fed Induction Generator Under Weak Grid[J]. CSEE Journal of Power and Energy Systems, 2025, 11(3): 1070-1079.DOI: 10.17775/CSEEJPES.2021.00760.
Impact of Dead-Time on Resonance in Doubly Fed Induction Generator Under Weak Grid
Subsynchronous resonance (SSR) and high-frequency resonance (HFR) are two phenomena that exist in a doubly fed induction generator (DFIG) system operated in a weak grid. Besides the aforementioned resonance
dead-time in the converter (rotor side converter (RSC) and grid side converter (GSC)) of the DFIG system can cause resonance at middle frequencies. The aforementioned resonance at middle frequencies can greatly degrade dynamic performance and cause instabilities in the DFIG system. Nevertheless
there is not enough research available in existing literature on resonance in the DFIG system
considering dead-time impact. This paper proposes a new method of resonance analysis in a DFIG system
taking dead-time effect into consideration and utilizing small-signal impedance modeling. Dead-time of the RSC and GSC will introduce distorted voltage into the rotor-and stator-side of the DFIG. Then
rotor-side impedance is modified by adding the effect of transfer function (impedance) from the distorted voltage to rotor current. Likewise
the stator-side impedance is modified by adding the effect of the transfer function (impedance) from distorted voltage to stator current. Thus
overall DFIG system impedance
as seen from the point of common coupling is changed. Finally
resonance is revealed by plotting the DFIG system impedance and weak grid impedance on the Bode plot. Additionally
resonance mitigation is impedance on the Bode plot. Additionally
resonance mitigation is exposed through the dead-time compensation (DTC) technique using an adaptive second-order bandpass filter. With the proposed technique
the resonance at middle frequencies is damped with zero probability of resonance reoccurrence. Finally
the validity and the accuracy of the proposed DTC techniques are validated using mathematical analysis and simulations in Matlab.
Cascaded Multiscale Modeling Method of Inertia-Controlled Wind Turbine for System Transient Mechanism Analysis
Identification of Crowbar Status for DFIG Short-Circuit Current Calculation
Converters' Loading Balance and Stability Verification for Doubly-Fed Induction Generators
A Survey on Model Predictive Control of DFIGs in Wind Energy Conversion Systems
Transient Stability Analysis and its Improvement of Isolated Renewable Energy Bases with VSC-DC Transmission
Related Author
Rui Zhang
Xiaoming Yuan
Jiabing Hu
Wenjia Xu
Yalou Li
Changqing Liu
Peipeng Zhou
Zutao Xiang
Related Institution
State Key Lab of Advanced Electromagnetic Engineering Technology, Huazhong University of Science and Technology
China Electric Power Research Institute
Anhui Province Key Laboratory of Renewable Energy Utilization and Energy Saving, School of Electrical Engineering and Automation, Hefei University of Technology