Ke Ji, Hui Pang, Shan Liu, et al. Impedance Analysis Considering Unstable Subsystem Poles for MMC-HVDC-based Wind Farm Integration System[J]. CSEE Journal of Power and Energy Systems, 2022, 8(2): 634-639.
DOI:
Ke Ji, Hui Pang, Shan Liu, et al. Impedance Analysis Considering Unstable Subsystem Poles for MMC-HVDC-based Wind Farm Integration System[J]. CSEE Journal of Power and Energy Systems, 2022, 8(2): 634-639.DOI: 10.17775/CSEEJPES.2020.04900.
Impedance Analysis Considering Unstable Subsystem Poles for MMC-HVDC-based Wind Farm Integration System
摘要
Abstract
Employing the AC/DC impedance analysis method
extensive research has been conducted on issues pertaining to harmonic resonance observed in wind farm-connected MMC-HVDC systems over the past 5 years. In general
this method divides the studied system into two subsystems at AC and DC sections. Subsequently
the impedance produced by these subsystems can be used to determine the system stability by implementing Nyquist criterion or generalized Nyquist stability criterion. However
the existing impedance analysis methods usually assume the subsystems to be stable and disregard certain special cases with potentially unstable subsystems
where the unstable poles of these subsystems must be evaluated before applying Nyquist criterion. In view of this consideration
a simplified method for identifying unstable subsystem poles is presented in this paper. Hence
the shortcoming of existing impedance analyses is rectified by considering the unstable subsystem poles. The proposed method and the stability analyses are validated by the electromagnetic transient simulation performed in PSCAD/EMTDC.
Frequency-Voltage Active Support Strategy for Hybrid Wind Farms Based on Grid-Following and Grid-Forming Hierarchical Subgroup Control
Sub-synchronous oscillations in power systems caused by grid-connected wind farms — A survey of mechanism studies
Control Strategy of Improved VSGs with Power Angle Compensation and Reactive Power Support Capability for Hybrid Multi-terminal HVDC Systems
Dynamic Energy Model and Sub-Synchronous Oscillation Mechanism for Direct-Drive Wind Farm Considering Interaction Between Generators
Quantifying Power Flexibility of Multisource Looped District Heating System Using Region-Based Method
Related Author
Haiyu Zhao
Qihang Zong
Hongyu Zhou
Wei Yao
Kangyi Sun
Yuqing Zhou
Jinyu Wen
Chen Chen
Related Institution
State Key Laboratory of Advanced Electromagnetic Technology, School of Electrical and Electronics Engineering, Huazhong University of Science and Technology
North China Electric Power University,, Beijing, CN
Queen's University Belfast,, Belfast, GB
School of Electrical Automation and Information Engineering, Tianjin University
State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University