Yunpeng Liu, Shilong Huang, Lei Zhu. Influence of humidity and air pressure on the ion mobility based on drift tube method[J]. CSEE Journal of Power and Energy Systems, 2015, 1(3): 37-41.
DOI:
Yunpeng Liu, Shilong Huang, Lei Zhu. Influence of humidity and air pressure on the ion mobility based on drift tube method[J]. CSEE Journal of Power and Energy Systems, 2015, 1(3): 37-41. DOI: 10.17775/CSEEJPES.2015.00033.
Influence of humidity and air pressure on the ion mobility based on drift tube method
摘要
Abstract
The measurement of ion mobility is important for calculating the corona loss of the transmission lines
and for establishing corona loss and ion current models that take humidity and air pressure into consideration. This paper describes a needle-ring corona discharge experiment setup based on a prior study
which simulates different humidity and air pressure conditions; it is observed that the execution of the ion gate is improved in this experiment from off-on-off to off-on to achieve higher ion current amplitude. Additionally
positive and negative ion mobility under different humidity and air pressure is obtained
with the positive ion mobility measurements in the range of 1.1126 to 1.9167 cm
2
/V·s
and the negative ion mobility measurements in the range of 1.3574 to 2.5643 cm
2
/V·s. The experimental results indicate that ion mobility decreases nonlinearly with increase in humidity
but trends towards saturation in the 30%-70% relative humidity range. Finally
a parameter correction method for calibrating the relationship among the ion mobility