Xuanyu Zhao, Huafeng Zhou, Di Shi, et al. On-line PMU-based transmission line parameter identification[J]. CSEE Journal of Power and Energy Systems, 2015, 1(2): 68-74.
DOI:
Xuanyu Zhao, Huafeng Zhou, Di Shi, et al. On-line PMU-based transmission line parameter identification[J]. CSEE Journal of Power and Energy Systems, 2015, 1(2): 68-74. DOI: 10.17775/CSEEJPES.2015.00021.
On-line PMU-based transmission line parameter identification
摘要
Abstract
China Southern Power Grid Company (CSG) recently developed and implemented an online PMU-based transmission line (TL) parameter identification system (TPIS). Traditionally
TL parameters are calculated based on transmission tower geometries
conductor dimension
estimates of line length
conductor sags
etc. These parameters only approximate the effect of conductor sag and ignore the dependence of impedance parameters on temperature variation. Recent development in PMU technology has made it possible to calculate TL parameters accurately. The challenges are that such an application requires highly accurate PMU data while the accuracy of PMU measurements under different working/system conditions can be uncertain. With a large number of PMUs widely installed in its system
CSG plans to improve and update the EMS database using the newly developed TPIS. TPIS provides an innovative yet practical problem formulation and solution for TL parameter identification. In addition
it proposes a new metric that can be used to determine the credibility of the calculated parameters
which is missing in the literature. This paper discusses the methodologies
challenges
as well as implementation issues noticed during the development of TPIS.