100Hz Protection Optimization Scheme of Rectifier Station Based on Station Domain Information
摘要
对于现有仅利用单一设备量测量信息进行故障判断的100 Hz保护
其动作响应存在一定的盲目性
在换流站交流区域故障时适应性不足。对此提出基于站域信息区分整流站直流区域故障和交流区域故障
实现100 Hz保护优化
赋予100 Hz保护识别整流站直流区域故障与交流区域故障的能力。基于100 Hz保护误动原因分析
提出换流母线基频负序电压与直流线路二次谐波电压的相关系数
构建整流站故障区域识别方法。仿真结果表明
该方法不受故障类型、故障位置、过渡电阻、故障初始角以及噪声干扰的影响
可靠性高。
Abstract
Aiming at the existing 100 Hz protection using only a single device measurement information for fault judgment
the action response of the protection is blind to a certain extent
and its adaptability is insufficient when the AC area of converter station fails. It is proposed to distinguish the DC area fault from the AC area fault of rectifier station based on station domain information
which realizes 100 Hz protection optimization and gives 100 Hz protection the ability to identify the DC area fault and the AC area fault of rectifier station. Based on the cause analysis of misoperation of 100 Hz protection
the correlation coefficient between the negative sequence voltage of converter bus fundamental frequency and the second harmonic voltage of DC line is proposed
and the fault area identification method of rectifier station is constructed. The simulation results show that the method is not affected by fault type