MA Yong-feng, ZHOU Ding-heng, ZHANG Zhi-hao, et al. In-situ test on vibro-replacement stone pile in large
petrochemical foundation treatment[J]. 2015, 36(S1): 327-333.
DOI:
MA Yong-feng, ZHOU Ding-heng, ZHANG Zhi-hao, et al. In-situ test on vibro-replacement stone pile in large
petrochemical foundation treatment[J]. 2015, 36(S1): 327-333.DOI: 10.16285/j.rsm.2015.S1.056.
In-situ test on vibro-replacement stone pile in large
petrochemical foundation treatment
Foundation treatment of large-scale refinery is very complex. In view of this condition
in-situ test of vibro-replacement stone pile was carried out. With static cone penetration test dynamic penetration
pile density was detected and saturated sand liquefaction was judged. Based on results of pressuremeter test
standard penetration test and heavy dynamic penetration test
foundation bearing capacity change and soil engineering characteristics change during construction process of vibro-replacement stone piles were analyzed. The bearing capacity of composite foundation was evaluated by static load test of single pile and composition foundation. The results show as follows. Firstly
vibro-replacement stone pile has a compaction effect on the sand soil of pile length range. Engineering characteristics and field uniformity has been improved apparently. Sand liquefaction possibility for pile length range can be eliminated. Secondly
static load test results show that the bearing capacity of composite foundation has reached the design requirement. Thirdly
the compaction effect on clay soil
which is under sand soil layer
is not apparent. And soil strength in some depth range even reduces. Finally
the bearing characteristics will not significantly be affected when no more than 5 m thickness of soft soil interlayer exists 10 m depth below the ground surface.