Error comparison and analysis of high-voltage current transformer based on different testing methods
There are various methods to test the error of high-voltage current transformer
however
there is little analysis on the difference and accuracy among testing results of these methods. The error of high-voltage current transformer is tested and compared with single-phase testing
absolute value calculation of the current error considering the influence of voltage and current error testing under rated voltage. And the reason of their differences is analyzed.The results show that voltage has a negative influence on ratio error and phase displacement of current transformer
and its effect is mainly predominant at currents less than 20% of rated current. The larger the current is
the smaller the influence will be
and the influence decreases gradually until it can be neglected with the increase of current. The current errors tested at low voltage are inaccurate at low current
and the absolute value of the variations of current error is much larger than the results tested at high voltage
as a result
the current error of high-voltage current transformer should be tested directly at rated primary voltage.