Method for evaluating voltage weak area of AC power system at DC receiving end considering sensitivity and static voltage stability margin[J]. 2019, 39(3): 1-8.
Method for evaluating voltage weak area of AC power system at DC receiving end considering sensitivity and static voltage stability margin[J]. 2019, 39(3): 1-8. DOI: 10.16081/j.issn.1006-6047.2019.03.001.
Method for evaluating voltage weak area of AC power system at DC receiving end considering sensitivity and static voltage stability margin
A method for evaluating voltage weak area of AC power system at DC receiving end considering both reactive-voltage sensitivity and static voltage stability margin is proposed
and the static voltage characteristics of load are considered during the calculation of sensitivity and static voltage stability. Firstly
the sensitivity of voltage at AC node to reactive power at DC node is calculated based on power flow equation of AC/DC power system
in which the load static voltage characteristics of load are considered. Secondly
the static voltage stability margin considering the load static voltage characteristics is calculated based on the continuation power flow. Finally
the voltage weak area of AC power system at DC receiving end is evaluated by reactive-voltage sensitivity combing with static voltage stability margin. Furthermore
the effects of different ZIP load ratios and DC control ways on evaluating voltage weak area of AC power system at DC receiving end are compared.