Fault analysis of mixed-voltage double-circuit lines partly on same tower under different grounding modes of neutral point
通过复合序网及求解方程组得到故障点短路电流。通过PSCAD软件对一中性点不同接地方式混压部分同塔双回线系统(220 kV/110 k V/35 k V)各种故障进行仿真验证
结果表明所提故障计算方法的精确性及实用性。
Abstract
Based on the sequential component method
the inter-line fault of mixed-voltage double-circuit lines partly on the same tower in neutral point directly grounding and indirectly grounding systems near substations is studied.Firstly
the zero-sequence mutual inductance between mixed-voltage double-circuit lines partly on same tower is eliminated
and the system is decoupled into comprehensive positive-
negative-and zero-sequence networks. According to wiring mode of three-winding transformers
the amplitude and phase angle of common impedance parts of the comprehensive positive-
negative-and zero-sequence networks are corrected
and the independent six-sequence network of mixed-voltage double-circuit lines partly on the same tower under different grounding modes of neutral points is obtained. The boundary condition of fault point is listed according to the fault types
and the short circuit current at fault point is obtained by the composite sequence network and its solution equations. Different types of faults in mixed-voltage(220 k V/110 kV/35 k V) double-circuit lines partly on same tower in neutral point directly grounded and indirectly grounded systems are simulated with PSCAD software
and the simulative results verify the accuracy and practicability of the proposed method.