In order to improve the DCS temperature protection logic
improve the reliability of the temperature protection in the thermal power plant
so as to reduce the temperature protection error action
no action caused by the unit non-stop or the unit equipment damage. Through the research and analysis of the temperature protection logic of a power plant
the logic shortcomings and desirable disadvantages are found from the perspective of logic optimization
and the logic shortcomings are optimized
so as to improve the reliability of temperature protection. The study found that the reset end of the RS trigger of temperature protection is generally automatic reset
but when the temperature remains high
after the automatic reset
the protection will trigger
resulting in non-stop accidents of the unit. By changing the reset end logic of the RS trigger
the reset output of the temperature data is only restored to the value nearly before the temperature mutation
i. e.
the temperature is restored to the original level
and the reliability of the temperature quality judgment is logically improved. The experimental results show that when the temperature is suddenly increased
the protection action will not be triggered for how long
which greatly improves the reliability of temperature protection
and the temperature protection misaction rate drops from 5% to 0%.