储琳, 张曦, 张子龙. Surge Fault Analysis of Centrifugal Chiller in Air Conditioning System of a Medical Experimental Center[J]. 2022, (1): 77-82.
DOI:
储琳, 张曦, 张子龙. Surge Fault Analysis of Centrifugal Chiller in Air Conditioning System of a Medical Experimental Center[J]. 2022, (1): 77-82. DOI: 10.16056/j.2096-7705.2022.01.012.
Surge Fault Analysis of Centrifugal Chiller in Air Conditioning System of a Medical Experimental Center
The surge of centrifugal chiller seriously affects the stability and service life of chiller. Fault analysis should be carried out in time when surge happen. The fault analysis can adopt the method of operation data comparison for preliminary judgment. In the surge fault analysis of centrifugal chiller in the air conditioning system of a medical experimental center
according to the structure
operation characteristics and surge mechanism of centrifugal chiller
through on-site investigation and operation data comparison
it is concluded that the cause of surge of chiller is too high condensation pressure
and the problem of too high condensation pressure is solved through the inspection and maintenance of peripheral equipment. Finally
the surge phenomenon of the unit is alleviated
and the feasibility of data analysis is verified
which provides a reference for technicians in analyzing and dealing with such faults.