朱晓云, 付猛. Comparison and Selection between High Water Collecting Tower and Conventional Natural Ventilation Cooling Tower[J]. 2021, (4): 106-109+116.
DOI:
朱晓云, 付猛. Comparison and Selection between High Water Collecting Tower and Conventional Natural Ventilation Cooling Tower[J]. 2021, (4): 106-109+116. DOI: 10.16056/j.2096-7705.2021.04.020.
Comparison and Selection between High Water Collecting Tower and Conventional Natural Ventilation Cooling Tower
In order to quickly select the appropriate type of cooling tower in the design process
taking an actual power plant as an example
a comprehensive technical and economic comparison is made on the ventilation heat and resistance
energy saving
noise reduction
operation mode of circulating water system and annual operation cost of 10 000 m
2
conventional natural ventilation cooling tower and 9 500 m
2
high water collection cooling tower with similar cooling effect
The comparative analysis shows that the high-level water collection cooling tower has the advantages of advanced technology and obvious effect of energy saving and noise reduction
but the construction
and operation are difficult and the investment is high. Conventional natural ventilation cooling tower has mature technology
low investment
simple construction and operation and convenient management
but the effect of energy saving and noise reduction is poor. The power plant can select the type of cooling tower suitable for its construction according to the advantages and disadvantages of conventional natural ventilation cooling tower and high-level water collection cooling tower. For areas with strict surrounding noise control
high-level water collection cooling tower can be selected. In order to save investment
conventional natural ventilation cooling tower can be selected in other areas.