SHAO Xingzhi, LUO Jingjing, JIN Shiyan, et al. Analysis and Suggestions on Continuous Overstep Tripping of Protection Caused by Secondary AC-DC Coupling[J]. Rural Electrification, 2026, (5): 61-66.
SHAO Xingzhi, LUO Jingjing, JIN Shiyan, et al. Analysis and Suggestions on Continuous Overstep Tripping of Protection Caused by Secondary AC-DC Coupling[J]. Rural Electrification, 2026, (5): 61-66.DOI: 10.13882/j.cnki.ncdqh.2602F021.
Analysis and Suggestions on Continuous Overstep Tripping of Protection Caused by Secondary AC-DC Coupling
This paper presents a case study of continuous overstep tripping of the medium-high voltage backup protection in a 110 kV main transformer caused by a 35 kV line fault and secondary AC-DC coupling faults of the transformer. Through fault dispatching
comprehensive substation equipment inspection
and root cause analysis
this paper identifies the reasons for the continuous overstep tripping of transformer protection. The study highlights issues in this case
including substandard quality of transformer live status indicators
non-standardized alarm information
flaws in secondary circuit design
and inadequate lightning protection measures on transmission lines. Corresponding improvement suggestions are proposed to prevent similar incidents
contributing to the safe and stable operation of the power grid.