This paper investigates a "latent" fault case in a 10 kV XLPE cable that exhibited severe localized overheating (71.6 °C) during infrared detection despite passing conventional insulation resistance and withstand voltage tests. By combining morphological analysis of the dissection and an equivalent circuit model
this study deeply explores the physical evolution mechanism of such defects. The findings indicate that local oxidation and the non-linear surge in resistivity of the semiconductive layer
caused by sheath damage
are the root causes of the fault. Unlike traditional partial-discharge-induced heating models
this paper proposes a mechanism of thermal generation driven by the synergistic effects of high-resistance leakage current and nonlinear dielectric loss. Theoretical derivations demonstrate that
within the defect microregion
electric field distortion and temperature rise form a positive feedback loop
leading to an exponential increase in local power density
while the macroscopic leakage current remains at the microampere level
thereby escaping detection by routine preventive tests. This study reveals the nonplused evolution characteristics of early latent thermal faults in cables and establishes the critical role of infrared thermography in condition-based maintenance of distribution networks.