To address the high cost of fault isolation in multi-terminal direct current (MTDC) systems integrating offshore wind power via diode rectifier units (DRUs)
a fault handling scheme based on a receiving-end diode-type modular multilevel converter (DMMC) is proposed. First
for bipolar short-circuit faults in DC submarine cables
the passive blocking of the receiving-end diodes and the coordinated isolation mechanism at the offshore end are clarified; for monopole-to-ground faults
the adaptive fault ride-through mechanism in a pseudo-bipolar configuration is analyzed. Then
the coupling process between diode natural turn-off and transient traveling waves in submarine cables is investigated. An equivalent short-circuit discharge circuit model is established
and an analytical expression for the maximum reverse overvoltage across the diode is derived based on the quarter-wavelength resonator theory. Finally
a ±500 kV/6 GW four-terminal DC collection electromagnetic transient model is built in PSCAD/EMTDC to validate the proposed scheme. The results show that
under a bipolar short-circuit fault
the series-connected diodes can achieve rapid current zero-crossing and passive blocking within 50 μs
while the DC bus voltage remains above 0.9 pu during the fault transient. Under a monopole-to-ground fault
uninterrupted system ride-through can be realized.
Online Detecting Winding Deformation of Power Transformer Based on Transient Overvoltage
Simulation and Test of Electromagnetic Interference with Electronic Current Transformer
Study on Fast Analysis Method Transient Fundamental Frequency Overvoltage of Wind Turbine Generators in Sending System when Serious Power Disturbances Occur in Large-capacity UHVDC
Auto-reclosing Control Strategy of Thyristors-based High Voltage DC Hybrid Circuit Breaker
Related Author
ZHA Xiaoming
SUN Jianjun
DAI Shuangyin
LI Qionglin
PENG Minxuan
PENG Neng
LI Zhaojiong
CHEN Xiaohan
Related Institution
State Grid Henan Electric Power Company
School of Electrical Engineering and Automation, Wuhan University
Hubei Key Laboratory of Power Equipment & System Security for Integrated Energy (Wuhan University)
State Key Laboratory of Power Transmission Equipment & System Security and New Technology, Chongqing University
School of Electrical Engineering, Dalian University of Technology