HE Meng, LI Guanghui, WANG Weisheng, et al. SVG控制模式对新能源场站宽频振荡作用机理分析及工程实践(一):阻抗建模与机理分析[J]. 2026, 52(9): 4081-4091.
DOI:
HE Meng, LI Guanghui, WANG Weisheng, et al. SVG控制模式对新能源场站宽频振荡作用机理分析及工程实践(一):阻抗建模与机理分析[J]. 2026, 52(9): 4081-4091.DOI: 10.13336/j.1003-6520.hve.20260405.
SVG控制模式对新能源场站宽频振荡作用机理分析及工程实践(一):阻抗建模与机理分析
摘要
随着新能源大规模并网,新能源场站宽频振荡事故频繁发生。新能源场站除了风电、光伏发电装备,还配置静止无功发生器(static var generator,SVG)。目前关于SVG控制模式对场站宽频振荡作用通路及主导环节定位的模型缺失、机理不清。该文首先构建了定无功功率/定交流电压不同模式下SVG小信号传递关系,建立相应的阻抗模型,并进一步构建了包含新能源发电、SVG、电网的三端口网络模型;然后,定量分析SVG不同控制模式阻抗特性差异产生原因,以及对系统阻抗的影响,并揭示了SVG控制模式对新能源场站振荡的作用规律;最后,基于MATLAB/Simulink仿真平台,开展了SVG不同控制模式对新能源场站宽频振荡影响的仿真实验,验证了分析结论的正确性。
Abstract
With the large-scale grid integration of renewable energy (RE) generation
frequent occurrences of broadband oscillations have been observed in RE plants. RE plants incorporate devices such as static var generators (SVG) besides wind turbines and photovoltaic (PV) generation units.Analytical models and mechanistic understanding remain deficient in characterizing the impact pathways and dominant contributing factors of SVG control modes on broadband oscillations in RE plants. This paper first constructs the small-signal transfer relations of SVG under different control modes (reactive power control mode and AC voltage control mode)
establishes a three-port network model comprising RE generation
SVG
and the power grid. Subsequently
quantitative analysis is conducted to determine the causes of impedance characteristics discrepancies under different SVG control modes and their impacts on system impedance
and the influence patterns of SVG control modes on RE plant oscillations is revealed. Finally
simulation experiments on the impact of different SVG control modes on broadband oscillations in RE stations were conducted based on the MATLAB/Simulink simulation platform
verifying the correctness of the analytical conclusions.
Nonlinear Active Disturbance Rejection Control of Static Var Generator with Cascaded Unit Considering Time-delay Factor
Topology and Control of High Power Current Source Converter SVG
Stray Inductance Extraction of SiC MOSFET Device Package and Test Platform
大规模集中式光伏并网场景下电力系统失步振荡中心迁移特性
Negative Sequence Treatment and Control Strategy for the Co-phase Interconnected Power Supply System of Traction Substation Group Based on Dd Transformer and SVG
Related Author
XU Dianguo
WU Liqiang
WU Jian
YAN Jichi
YANG Rongfeng
YU Yannan
WU Haitao
WANG Zhihe
Related Institution
College of Electrical and Control Engineering, Heilongjiang University of Science and Technology
Beijing Kerui Yuanteng Measurement and Control Technology Co., Ltd.
Department of Electrical Engineering, Harbin Institute of Technology
The Electrical Power College, Inner Mongolia University of Technology
State Key Laboratory of Alternate Electrical Power System With Renewable Energy Sources,North China Electric Power University