The flying motion behavior of linear metallic particles is a key factor contributing to insulation failure in direct current (DC) gas insulated switchgear (GIS). To investigate how the movement of these linear metallic particles in DC-GIS affects their trajectory distribution and adsorption characteristics
a transparent experimental cavity containing insulators is constructed. A YOLO target detection model is then used to study the entire process
from the lifting to the adsorption
of these linear metallic particles under DC voltage. The results show that
under a positive voltage
the metallic particles primarily exhibit reciprocating motion between the electrodes
accompanied by a ‘jumping firefly’ phenomenon. Increasing the voltage amplitude increases the number of firefly movements. Conversely
under a negative voltage or with an increase in the metallic particles’ length
the number of swing firefly movements of metallic particles increases
which reduces the time ratio of metallic particles’ movements in the upper part of the cavity. Adsorption of the metallic particles typically occurs during their flight. Specifically
the insulator’s convex surface is more prone to adsorption when the particles are in a jumping firefly state
and they may roll along the insulator surface during this process. In contrast
the insulator’s concave surface is more readily adsorbed when the particles are in a swing firefly state. The findings of this research can provide reference for the protection and treatment of metallic particles in DC-GIS.