In order to accurately diagnose the characteristics of vacuum arcs and to further investigate their key regulatory mechanisms
thereby improving the performance and reliability of vacuum switching devices
this study established an optical diagnostic system for Cu II (Cu+) excitation temperature in vacuum arcs based on emission spectroscopy
and analyzed the 2D spatiotemporal distribution of Cu+ excitation temperature and its dependence on current amplitude
contact gap
and contact material. Experimental results show the near-anode temperature synchronizes with the sinusoidal current waveform
while the near-cathode temperature remains stable at (12 500±1 000) K for 0~6 ms before decreasing with current density. The arc column temperature exhibits distinct current-dependent characteristics with trapezoidal variation at 8 kA and U-shaped variation at 14/20 kA. Spatially
the axial temperature distribution displays a linear monotonic increase from anode to cathode at 8 kA
evolving into a pattern with higher temperatures at both ends at 14/20 kA
while the radial distribution transforms from a central high-temperature zone to an edge annular high-temperature zone with increasing current. Current amplitude affects temperature differently across regions: near-anode temperature increases linearly with current
and arc column shows opposite trend
while near-cathode temperature rises below 16 kA then stabilizes
demonstrating saturation. Reducing contact gap forms distinct jet structures with 25%~30% higher core temperatures. Increasing Cr content significantly lowers Cu+ excitation temperature. These findings provide an experimental basis for understanding and controlling vacuum arc plasma characteristics.