In the detection of partial discharge (PD) in gas-insulated equipment
the traditional fiber optic sensing system with a single-ended output configuration suffers from severe attenuation of signal intensity as the transmission distance increases
along with insufficient sensitivity. This paper investigates the influence of the relative position between the photosensitive point and the PD source on the signal intensity in a single-ended output fiber optic sensing system. On this basis
a design scheme for a dual-ended optical coupling fiber optic sensing system is proposed
where the sensing performance is optimized by introducing an additional signal increment term. Furthermore
a comparative analysis of the signal intensity characteristics of the two systems is conducted. Experimental results show that
compared with the single-ended output sensing system
the dual-end optical coupling sensing system exhibits significant advantages in signal intensity due to the introduction of the additional signal increment term. Specifically
for a 20 cm fluorescent optical fiber
the number of detectable PD pulses is increased by approximately 26.57%
the average discharge amplitude by about 27.55%
and the maximum discharge amplitude by roughly 21.63%. For an optical fiber with a length of 3 m
the above-mentioned indicators are increased by approximately 735%
118.4%
and 311.1% respectively. In addition
the dual-end transmission system also demonstrates good potential for PD source localization
with the error between the test data and the reference value not exceeding 3%. The research results of this paper provide a reference for optimizing the PD optical fiber detection sensitivity of gas-insulated equipment.