With the rapid development of ultra-high voltage (UHV) power grids
electromagnetic environmental issues caused by radio interference (RI) from transmission lines have become increasingly prominent. Therefore
two-year monitoring data from the long-term observation station of the 750 kV transmission line in Guanting were utilized to conduct outlier processing of RI
andinfluencing factors under different weather conditions were analyzed. The results demonstrate that: (1) The proposed PSO-DELM method can be adopted to effectively detect RI outliers and achieve effective imputation of missing values
and the K-S test p value of the filled value is 0.398 4; (2) Under fair weather
RI exhibits a positive correlation with the ambient temperature
while atmospheric pressure exerts a significant inhibitory effect on RI; (3) The L50 value of the RI within one day in rainy days varies from 51.5 dB to 66.0 dB in this region
and rainfall intensity and relative humidity dominate RI during rainy conditions
both showing positive correlations
and RI stabilizes after a fluctuation adjustment phase post-rainfall; (4) The L50 value of the RI within one day in snowy weather varies from 56.5 dB to 65.5 dB in this region
and snowfall intensity strongly correlates with RI during snowy weather
followed by a prolonged adjustment period post-snowfall. This research provides a scientific basis for controlling RI in UHV transmission lines.