The complex internal structure of a transformer introduces difficulties in identifying the acoustic propagation paths from partial discharge (PD) sources to sensors. As a result
time-delay information alone is insufficient for intuitively reconstructing the spatial location of PD sources
ultimately increasing localization errors. To improve the accuracy of acoustic PD localization in complex multipath propagation conditions
this paper proposes a method for distinguishing direct and non-direct acoustic waves in transformer acoustic signals
and analyzes the impacts of these two propagation modes on localization errors. First
the physical mechanisms of direct and non-direct waves formation are analyzed
and their differences in waveform morphology are described. Direct waves exhibit a steep rising edge at the moment of arrival
with dominant high-frequency content and a rapid amplitude decay after the peak. To capture these differences
four representative features are constructed from both time and frequency domains: the peak-to-rise time ratio
signal kurtosis
energy decay rate
and the ratio of high-frequency to low-frequency energy. These features are then used to train a support vector machine (SVM) classifier to accurately identify direct and non-direct wave signals. Subsequently
acoustic PD signal acquisition and localization experiments are conducted on a laboratory-scale 110 kV transformer platform. Experimental results demonstrate that the proposed SVM-based classification method achieves recognition rates of 88.3% and 84.6% for direct and non-direct waves
respectively. When using non-direct waves for PD localization
the average positioning error reaches 75.23 cm with a standard deviation of 32.34 cm. In contrast
localization based on direct waves yields a significantly lower average error of just 6.66 cm with a standard deviation of 2.97 cm
reducing the positioning error by 68.57 cm and the standard deviation by 29.37 cm.