Dissolved gas analysis in oil is one of the most effective methods for fault diagnosis oil-immersed transformers. Therefore
detection of characteristic gases in oil is essential to maintain the power transformer normal operation. In this paper
CeO2-based gas-sensitive materials were prepared using a one-step hydrothermal synthesis
and the successful preparation of the materials was verified by XRD
SEM and XPS characterization techniques. Based on the established gas-sensitive platform
the temperature-response characteristics
mole fraction-response characteristics
repeatability
response-recovery characteristics and selectivity of the Cu-CeO2 sensor for C2H4 were tested. It is found that the optimal operating temperature of Cu-CeO2 for C2H4 is 180 ℃
and the response value of 100×10-6 mole fraction C2H4 is 66%. The response time and recovery time are 18 s and 15 s
respectively. The sensor exhibits excellent interference resistance against C2H2
C2H6
H2
CH4
CO2
and CO gases. Furthermore
based on the first-principal calculation
the gas-sensing mechanism of the Cu-CeO2 sensor for the oil-immersed characteristic gases was analyzed by calculating the adsorption parameters
density of states
and electron density of the adsorption system. The results indicate that the Cu-CeO2 crystal surface exhibits strong chemical adsorption only for C₂H₄
with an adsorption energy of -1.488 eV
and the calculated results are consistent with the findings from macroscopic gas-sensing experiments. Thus
the gas-sensing performance analysis and theoretical calculations in this paper provide a theoretical basis and experimental support for the development of low-power
high-sensitivity
and fast-response C2H4 sensor for the characteristic gas in oil detection.