Simulation Analysis of Temperature and Current Carrying Capacity of Submarine Cables in the Dual Loop Heterogeneous Landing Section Considering Circulation
|更新时间:2026-02-25
|
Simulation Analysis of Temperature and Current Carrying Capacity of Submarine Cables in the Dual Loop Heterogeneous Landing Section Considering Circulation
ZHOU Yuanxiang, FU Xinya, LYU Weiwei, et al. Simulation Analysis of Temperature and Current Carrying Capacity of Submarine Cables in the Dual Loop Heterogeneous Landing Section Considering Circulation[J]. 2025, 51(6): 2748-2758.
DOI:
ZHOU Yuanxiang, FU Xinya, LYU Weiwei, et al. Simulation Analysis of Temperature and Current Carrying Capacity of Submarine Cables in the Dual Loop Heterogeneous Landing Section Considering Circulation[J]. 2025, 51(6): 2748-2758. DOI: 10.13336/j.1003-6520.hve.20241944.
Simulation Analysis of Temperature and Current Carrying Capacity of Submarine Cables in the Dual Loop Heterogeneous Landing Section Considering Circulation
Submarine cables are an important component of power grid construction
and the size of metal sheath circulation and armor circulation is an important reference for the design and operation of submarine cable engineering. In the existing literature
the overall line circulation size is not considered in the calculation of the temperature-field current-carrying capacity of submarine cables
thus the accuracy is affected. Therefore
we established a field circuit coupling calculation model that considers the overall laying conditions of the metal sheath
armor circulation
and cable temperature distribution. The circulation of the three-phase circuit of the double circuit heterogeneous submarine cable is calculated by the MATLAB
and the electromagnetic thermal current multi-physical-field coupling simulation model of the double-circuit heterogeneous submarine cable temperature distribution is established by finite element simulation software with current as the coupling term. The current-carrying capacity and temperature changes of the double-circuit heterogeneous landing section submarine cable considering the effect of circulation are studied
and an optimization scheme for the landing section current-carrying capacity considering both environmental heat dissipation conditions and internal circulation losses is proposed. The research results indicate that the simulation model considering the overall line circulation has higher computational accuracy compared to traditional simulation
and the maximum error can be reduced from 9.47% to 0.63%. When the air velocity is greater than 0.5 m/s
the convective heat flux in the cable trench of the landing section tends to saturate
causing the overall trend of the cable's current-carrying capacity and insulation temperature difference to first increase sharply and then stabilize. When adopting the optimization scheme of reducing circulation by adding seawater
the current-carrying capacity of oil filled submarine cables and XLPE submarine cables can be increased by 49.9% and 49.6%
respectively. This study can provide reference and ideas for the calculation of current-carrying capacity and engineering laying of landing section submarine cables.