In order to clarify the comprehensive operating range of grid-connected inverters under weak grid conditions considering multiple constraints
firstly
we analyzed the critical short-circuit ratio (SCR) of the grid-connected system under three individual constraints
namely
voltage limit violation
maximum power transfer
and small-signal stability. Subsequently
we put forward a comprehensive critical short-circuit ratio (CSCR) by integrating these three constraints
while revealing the dominant constraint determining the system’s CSCR. Then
the terminal voltage compensation strategy was adopted to re-evaluate the CSCR of the compensated system. Research results demonstrate that
in uncompensated scenarios
the system’s CSCR is mainly constrained by voltage limit violation. After implementing terminal voltage compensation targeting this primary constraint
the system only needs to consider small-signal stability constraints
thus the CSCR is reduced and the overall operating range is expanded. Simulations and hardware-in-the-loop experiments verify the correctness of the theoretical analysis.