Analysis and Breaking Requirements of Fault Current Fed by High-capacity Synchronous Generator
The existing high-capacity generator circuit breaker (GCB) relies on SF6 arc extinguishing technology
which is not environmentally friendly
has slow breaking speed
and has been monopolized by foreign companies. To clarify the requirements of large-capacity GCB at the system level and guide the development of environmentally friendly GCB
this paper studies the mechanism of delayed current zero appearing in the fault current fed by the large synchronous generator. It is found that the strong magnetic coupling effect between damping winding and stator winding is the main cause of delayed current zero
rather than the traditional thinking of high reactance to resistance ratio (X/R); The influence of damping winding material
fault phase angle
excitation state and speed on the amplitude and delayed current zero of the fault current is revealed. Taking a 1200MW practical nuclear power unit as an example
a simulation model based on the finite element method is constructed to verify relevant findings. The special requirements of large-capacity GCB are summarized. The research conclusions can guide and guide developing environmentally friendly large-capacity GCB.