A Comprehensive Reclosing Strategy for DC Distribution Grid Based on Power Flow Controller Signal Injection
为避免直流断路器(DC circuit breaker,DCCB)在永久性故障下重合闸而对系统造成二次冲击,同时针对不同故障类型选择不同的重合闸策略,提出一种基于串并联型潮流控制器(series-parallel power flow controller,SP-PFC)主动信号注入的直流配电网综合重合闸策略。首先,建立了含SP-PFC的直流配电网故障分析模型,分析了SP-PFC在故障期间吸收的故障能量;然后,为实现SP-PFC主动信号注入,设计了SP-PFC潮流控制、旁路控制、限流控制、闭锁控制和信号注入控制的逻辑框图和时序配合逻辑。通过SP-PFC主动注入高频电压脉冲信号,根据变分模态分解算法提取特征分量实现故障性质识别。在此基础上,根据故障期间线路两侧电流特征识别极对地、极对回线和极对极故障,结合瞬时性和永久性故障的识别,实现不同故障类型下的DCCB综合重合闸。最后,在Matlab/Simulink中搭建了含SP-PFC的直流配电网仿真模型,验证了所提策略的有效性。
Abstract
To avoid the DC circuit breaker reclosing on a permanent fault and causing a secondary impact on the system
and select different reclosing strategies for different fault types
a comprehensive reclosing strategy for DC distribution grid based on series-parallel power flow controller (SP-PFC) active signal injection is proposed. Firstly
a fault analysis model of the DC distribution grid containing SP-PFC is established
and the fault energy absorbed by SP-PFC during the fault is analyzed; Besides
to achieve the SP-PFC active signal injection
the logic block diagram and timing coordination logic of the SP-PFC power flow control
bypass control
current limiting control
blocking control and signal injection control are designed. High-frequency voltage signals are actively injected through SP-PFC
and then feature components are extracted according to the variational mode decomposition algorithm to realize fault property identification. On this basis
the identification of pole-to-ground
pole-to-dedicated-metallic- return and pole-to-pole faults based on current characteristics on both sides of the line during a fault
combined with identification of transient and permanent faults
enables DCCB comprehensive reclosing under different fault types. Finally
a simulation model of the DC distribution grid containing SP-PFC is built in MATLAB/Simulink to verify the correctness and effectiveness of the proposed strategy.