High-bandwidth Composite Control Strategy and Parameter Optimization Design Method of Independently Controlled Neutral Modules for Three-phase Four-wire Inverters
|更新时间:2026-10-05
|
High-bandwidth Composite Control Strategy and Parameter Optimization Design Method of Independently Controlled Neutral Modules for Three-phase Four-wire Inverters
ZHAO Jingtao, LEI Jiaxing, ZHENG Shu, et al. High-bandwidth Composite Control Strategy and Parameter Optimization Design Method of Independently Controlled Neutral Modules for Three-phase Four-wire Inverters[J]. 2026, 46(3): 1165-1177.
DOI:
ZHAO Jingtao, LEI Jiaxing, ZHENG Shu, et al. High-bandwidth Composite Control Strategy and Parameter Optimization Design Method of Independently Controlled Neutral Modules for Three-phase Four-wire Inverters[J]. 2026, 46(3): 1165-1177.DOI: 10.13334/j.0258-8013.pcsee.251275.
High-bandwidth Composite Control Strategy and Parameter Optimization Design Method of Independently Controlled Neutral Modules for Three-phase Four-wire Inverters
Three-phase four-wire inverters with an independently controlled neutral module have the advantages of small zero-sequence current and mutual decoupling of output neutral point voltage and three-phase voltage control. Maintaining stable neutral point voltage is fundamental to their normal operation. The traditional proportional-integral (PI) dual-loop control strategy is constrained by its limited bandwidth
resulting in inadequate suppression of midpoint voltage fluctuations. This can easily cause output common-mode disturbances and degrade waveform quality. To address this
this paper proposes a neutral point voltage control strategy based on the inner-loop state feedback (SF) and outer-loop PI composite
as well as a control parameter optimization design method driven by target response. The proposed control strategy establishes a refined mathematical model of the controlled object in the discrete domain. Based on a holistic system design philosophy
it derives analytical expressions for all control parameters by reverse-engineering the preset target transfer function. Furthermore
it quantifies the relationship between the system control bandwidth and the positions of closed-loop zeros and poles. Based on this
the system’s ability to suppress low-frequency components of zero-sequence current under different control bandwidths is investigated
as well as the effects of sampling delay and measurement noise on control system performance. This provides guidance for the optimal design of control parameters in practical applications. At the same time
the impact of wide variations in filter parameters on the closed-loop control performance of the system is analyzed. Experimental results demonstrate that the proposed method can significantly increase the control bandwidth without amplifying noise
thereby effectively suppressing midpoint voltage fluctuations under asymmetric/ harmonic load disturbances and improving output waveform quality