FAN Xiaoqing, DUAN Liqiang, WANG Qiushi, et al. Performance Analysis of New CCHP System With Organic Rankine Cycle Driven by Solar Thermal Energy[J]. 2026, 46(14): 5947-5958.
DOI:
FAN Xiaoqing, DUAN Liqiang, WANG Qiushi, et al. Performance Analysis of New CCHP System With Organic Rankine Cycle Driven by Solar Thermal Energy[J]. 2026, 46(14): 5947-5958.DOI: 10.13334/j.0258-8013.pcsee.251211.
Performance Analysis of New CCHP System With Organic Rankine Cycle Driven by Solar Thermal Energy
为提高太阳能梯级利用效率,该文提出3种基于不同热力循环结构的太阳能热驱动冷热电联供(combined cooling,heating and power,CCHP)系统,分别为亚临界有机朗肯循环(organic Rankine cycle,ORC)、超临界-亚临界ORC及再热超临界-亚临界ORC。基于Aspen Plus软件建立系统性能分析模型,对比不同CCHP系统性能并研究关键参数对最优系统性能影响规律。结果表明,相较于其他两种CCHP系统,集成再热超临界-亚临界ORC的CCHP系统(the CCHP system integrated with reheat supercritical-subcritical organic Rankine cycle,RSSORC-CCHP)发电效率分别提高25.55%、3.4%;㶲效率分别提高20.42%、3.6%,具有最佳热力性能,其原因主要是超临界ORC优异的热源匹配能力及再热过程降低的不可逆损失。对RSSORC-CCHP系统关键参数的敏感性分析结果表明,当工质一级透平入口温度和出口压力分别为380℃和1 MPa,S-ORC与ORC吸热比例为2.3时,系统净输出功率及发电效率最优;当太阳能直接法向辐照度(direct normal irradiance,DNI)变化时,RSSORC- CCHP系统的发电量、制冷量和供热量先增大后减小。研究结果将为更高效利用太阳能提供新思路和新途径。
Abstract
To improve the cascade utilization efficiency of solar energy
this study proposes three solar-thermal-driven combined cooling
heating and power (CCHP) systems based on different thermodynamic cycle configurations including subcritical organic Rankine cycle (ORC)
supercritical- subcritical ORC
and reheat supercritical-subcritical ORC. The system performance analysis model is established using Aspen Plus software. Different CCHP systems are compared in terms of thermal performance
and the effects of key parameters on the optimal system’s performance are analyzed. The results show that compared with the other two systems
the CCHP system integrated with the reheat supercritical-subcritical organic Rankine cycle (RSSORC-CCHP) has the best thermal performance
with power generation efficiency improvements of 25.55% and 3.4%
and exergy efficiency enhancements of 20.42% and 3.6%
respectively. These improvements are mainly attributed to the excellent heat source matching capability of the supercritical ORC and the reduced irreversibility during the reheat process. Sensitivity analysis results of the RSSORC-CCHP system show that the RSSORC- CCHP system achieves optimal net power output and power generation efficiency when the inlet temperature and outlet pressure of the first-stage turbine are 380℃ and 1 MPa
respectively
and the heat absorption ratio of the S-ORC to ORC is 2.3. Furthermore
with the change of direct normal irradiance (DNI) of solar energy
the power
cooling