Thermal Deviation Detection Method for Heat Transfer Surfaces in a 660 MW Opposed-Firing Boiler Based on Historical Operation Data and Euclidean Distance
|更新时间:2026-06-30
|
Thermal Deviation Detection Method for Heat Transfer Surfaces in a 660 MW Opposed-Firing Boiler Based on Historical Operation Data and Euclidean Distance
Power Generation TechnologyPages: 1-9(2026)
作者机构:
1.福建华电邵武能源有限公司,福建省 邵武市 354000
2.华电电力科学研究院有限公司,浙江省 杭州市 310030
3.煤燃烧与低碳利用全国重点实验室(华中科技大学),湖北省 武汉市 430074
作者简介:
基金信息:
National Key Research and Development Program of China(2023YFB4102903);2021 AI Innovation Task Challenge Program of the Ministry of Industry and Information Technology(CHDKJ22-01-126)
LIN Zengwen,ZENG Zhenrong,WENG Peihuang,et al.Thermal Deviation Detection Method for Heat Transfer Surfaces in a 660 MW Opposed-Firing Boiler Based on Historical Operation Data and Euclidean Distance[J].Power Generation Technology,
LIN Zengwen,ZENG Zhenrong,WENG Peihuang,et al.Thermal Deviation Detection Method for Heat Transfer Surfaces in a 660 MW Opposed-Firing Boiler Based on Historical Operation Data and Euclidean Distance[J].Power Generation Technology,DOI:10.12096/j.2096-4528.pgt.25469.
Thermal Deviation Detection Method for Heat Transfer Surfaces in a 660 MW Opposed-Firing Boiler Based on Historical Operation Data and Euclidean Distance
Under the national strategic goals of carbon peak and carbon neutrality
coal-fired power units frequently participate in deep peak-shaving operations at low loads
during which uneven flow distribution and combustion bias in the boiler heating surfaces cause thermal deviations
thereby increasing the risk of tube bursts due to water wall overheating. Conventional wall temperature monitoring methods
based on the enthalpy change of the working fluid
exhibit hysteresis and have difficulty in differentiating between inherent temperature distribution patterns and abnormal operational deviations. To address this
a thermal deviation discrimination method based on historical data and Euclidean distance is proposed for a 660 MW ultra-supercritical opposed-firing boiler.
Methods
2
Through analyzing the wall temperature of the main heating surfaces of the boiler
the operating load range is divided into intervals and a benchmark temperature database is constructed. Characteristic temperatures are extracted to eliminate the influence of overall temperature fluctuations. Furthermore
a thermal deviation index is established to quantify real-time deviations
and the method is applied in practice.
Results
2
Significant temperature differences exist among the tube panels of the heating surfaces
and this is especially apparent in the high-temperature reheater. The fluctuations in wall temperature consist of two parts: one is the inherent deviation arising from the system’s own characteristics
and the other is the fluctuating deviation brought about by adjustments in the operating mode.
Conclusions
2
The proposed method successfully identifies both the inherent deviations of the equipment and the operational fluctuating deviations
and it provides a real-time discrimination basis for boiler safety early-warning systems
ensuring operational safety under deep peak-shaving conditions.
LI X C , CHEN Y G , CAO J B , et al . Research on optimization strategy of power supply structure in Shanghai [J ] . Power Generation Technology , 2019 , 40 ( 1 ): 40 - 45 .
National Bureau of Statistics of China . Statistical communique of the People’s Republic of China on the 2024 national economic and social development [N ] . People’s Daily , 2025-03-01 (5).
LI F Q , PAN H Y , XIE L B , et al . Adjustment of thermal deviation for 350 MW supercritical opposed firing boiler [J ] . Hongshui River , 2025 , 44 ( 2 ): 119 - 123 .
ZHANG H , SUN B , CAO J H . Analysis of reheat steam temperature deviation of 1 000 MW double reheat ultra-supercritical units [J ] . Electric Power Technology and Environmental Protection , 2019 , 35 ( 1 ): 46 - 48 .
FAN Z M . Analysis of high temperature reheater deviation of external bed of 660 MW supercritical CFB boiler [J ] . Journal of Electric Power , 2022 , 37 ( 6 ): 553 - 560 .
CUI Z G , LIU H Q . Research on supercritical boiler heating surface oxide skin preventing and controling measures [J ] . Electric Power Technology and Environmental Protection , 2014 , 30 ( 4 ): 56 - 57 .
PAN Z C . Research on thermal deviation characteristics and optimization of an ultra-supercritical boiler based on coupled combustion and steam-side simulation [D ] . Nanjing : Southeast University , 2023 .
CHANG W , XU X , WEI R , et al . Analysis of influence of deep peak shaving on heating surface tubes of coalfired power units [J ] . Electric Power Technology and Environmental Protection , 2022 , 38 ( 6 ): 458 - 466 .
YAN X R , HU Z Y , ZHANG P W , et al . Research and application of operation flexibility improvement technology for coal-fired power unit [J ] . Power Generation Technology , 2024 , 45 ( 6 ): 1074 - 1086 . doi: 10.12096/j.2096-4528.pgt.24170 http://dx.doi.org/10.12096/j.2096-4528.pgt.24170
ZHANG X R , SONG Y Y , ZHOU Y J , et al . Hydrodynamic characteristics of deep peak shaving and calculation of water wall thermal deviation of supercritical circulating fluidized bed boiler [J ] . Proceedings of the CSEE , 2024 , 44 ( 15 ): 6047 - 6057 .
QIN Y , LI D B , QIN W , et al . Simulation study on heat transfer characteristics of water-cooled wall of ultra-supercritical boiler based on ebsilon software [J ] . Journal of Engineering for Thermal Energy and Power , 2025 , 40 ( 2 ): 76 - 84 .
JIA T K . Wall temperature calculation and over-temperature prediction of supercritical boiler superheater [D ] . Beijing : North China Electric Power University , 2022 .
ZHAO N N , LI P , HUANG W Q , et al . Research on wall temperature distribution characteristics of high temperature reheater in 1 000 MW ultra supercritical boiler [J ] . Boiler Technology , 2025 , 56 ( 1 ): 35 - 41 .
XU H H , SHAO G P , E C L , et al . Research on China’s future energy system and the realistic path of energy transformation [J ] . Power Generation Technology , 2023 , 44 ( 4 ): 484 - 491 . doi: 10.12096/j.2096-4528.pgt.23002 http://dx.doi.org/10.12096/j.2096-4528.pgt.23002
HONG M , CHAE H , KIM W C , et al . Failure analysis of a water wall boiler tube for power generation in a district heating system [J ] . Metals and Materials International , 2019 , 25 ( 5 ): 1191 - 1201 . doi: 10.1007/s12540-019-00267-6 http://dx.doi.org/10.1007/s12540-019-00267-6
MA F X . Research on fault source diagnosis of boiler reheater temperature deviation based on causal inference [D ] . Hangzhou : China University of Metrology , 2023 .
ZHANG Q B , ZHOU Q F . Research on the development path of China’s thermal power generation technology based on the goal of “carbon peak and carbon neutralization” [J ] . Power Generation Technology , 2023 , 44 ( 2 ): 143 - 154 . doi: 10.12096/j.2096-4528.pgt.22092 http://dx.doi.org/10.12096/j.2096-4528.pgt.22092
LI H , LIU D , YAO D Y . Analysis and reflection on the development of power system towards the goal of carbon emission peak and carbon neutrality [J ] . Proceedings of the CSEE , 2021 , 41 ( 18 ): 6245 - 6259 .
PAN X G , TANG Q , CHANG S B , et al . Research progress of intelligent,efficient and safe operation of coal-fired power plants based on wall temperature monitoring [J ] . Boiler Technology , 2025 , 56 ( 3 ): 14 - 22 .
TANG C . Online wall temperature monitoring of high-temperature superheater in a supercritical w-shaped flame boiler under the influence of in-tube corrosion [D ] . Chongqing : Chongqing University , 2023 .
WU W T . Research on modeling of boiler combustion system and steam temperature regulation for a 1000 mw ultra-supercritical unit [D ] . Beijing : North China Electric Power University , 2022 .
TALER J , ZIMA W , OCŁOŃ P , et al . Mathematical model of a supercritical power boiler for simulating rapid changes in boiler thermal loading [J ] . Energy , 2019 , 175 : 580 - 592 .
Autoencoder-Based Modeling for Fouling Monitoring on Boiler Heating Surfaces
Research on Performance Optimization of Transient Load Change Process in Coal-Fired Power Units
Analysis of Influence of Flue Gas Recirculation on Thermodynamic Performance and Economic Efficiency of 125 MW Supercritical CO2 Coal-Fired Power Generation Unit
Effects of Variable-Flow Water Distribution on Cooling Performance of Wet Cooling Towers and Its Optimization
Analysis of Influence of Coal-Ammonia Co-firing on the Heat Transfer Characteristics of Heating Surfaces in Coal-Fired Boiler
Related Author
CHEN Gang
FANG Qingyan
ZHANG Cheng
TAN Peng
WANG Xinyue
WANG Ke
CHEN Weixiong
CHEN Lu
Related Institution
Department of Thermal Energy and Power Engineering, School of Energy and Power Engineering, Huazhong University of Science and Technology
Shanghai Special Equipment Supervision and Inspection Institute, Putuo District
Key Laboratory of Thermal-Fluid Science and Engineering of Ministry of Education, Xi’an Jiaotong University
Guoneng Jinjie Energy Co., Ltd.
China Energy Digital Technology Group Co., Ltd., Chaoyang District