Kaiyun ZHENG. Study on Cold End Temperature Optimization of Supercritical CO2 Cycle[J]. Power Generation Technology, 2021, 42(2): 261-266.
DOI:
Kaiyun ZHENG. Study on Cold End Temperature Optimization of Supercritical CO2 Cycle[J]. Power Generation Technology, 2021, 42(2): 261-266. DOI: 10.12096/j.2096-4528.pgt.19149.
Study on Cold End Temperature Optimization of Supercritical CO2 Cycle
cycle has a high cold end temperature. Optimizing the cold end temperature plays an important role in improving the cycle efficiency. In order to obtain the best annual average efficiency
it is necessary to introduce artificial refrigeration to make the supercritical CO
2
cycle run at a more optimized cold end temperature. For the supercritical CO
2
recompression cycle with parameters of 550℃/20MPa
the annual average cycle efficiency under different cold end temperature of 5 to 35℃
with the combination of natural cooling and artificial refrigeration was analyzed by thermodynamic method
and the feasibility and economic analysis of the co
ld end temperature optimization method were studied as well. The annual average efficiency of the unit can be improved by choosing the optimal cold end temperature and combining natural cooling with artificial refrigeration. For northern China
the cold end temperature optimization method has better feasibility. The artificial refrigeration increases the investment of unit equipment
but the improvement of operation efficiency brings more power generation revenue and moreover increases the net income of the unit during its life cycle.
ZHENG K Y. Analysis of current status and trend of research and development on supercritical carbon dioxide power cycle[J]. Energy Engineering, 2017(5): 31-37.
DOSTAL V. A supercritical carbon dioxide cycle for next generation nuclear reactors[D]. Massachusetts: Massachusetts Institute of Technology, 2004.
AKBARI A D, Mahmoudi S M S. Thermoeconomic analysis & optimization of the combined supercritical CO 2 (carbon dioxide) recompression Brayton/organic Rankine cycle[J ] . Energy, 2014, 78: 501-512.
SONG J, LI X S, REN X D, et al. Performance analysis and parametric optimization of supercritical carbon dioxide (S-CO 2 ) cycle with bottoming organic Rankine cycle (ORC)[J ] . Energy, 2018, 143: 406-416.
MS S, ATA D A, MARC R. Thermoeconomic analysis and optimization of a new combined supercritical carbon dioxide recompression Brayton/Kalina cycle[J]. Sustainability, 2016, 8(10): 1079.
SUN H, XU X, LIU S J, et al. Thermal design and test verification of the evaporator for ORC power generating system[J]. Huadian Technology, 2019, 41(4): 59-62.
PRASHANT S, TY N, TURCHI C. Thermal desalination as cooling for a supercritical carbon dioxide Brayton cy cle[C ] //Proceedings of the 6th International Supercritical CO 2 Power Cycles Symposium. Pittsburgh, 2018: 1-9.
LI H C. Some suggestions on development concentrating solar power in China[J]. Electric Power Technology and Environmental Protection, 2017, 33(1): 57-58.
FRANCESCO C, GIACOMO G, DAVID S, et al. Supercritical carbon dioxide cycles for power generation: a review[J]. Applied Energy, 2017, 195: 152-183.
ZHENG K Y, HUANG Z Q. Study on hybrid geothermal-solar energy system with supercritical carbon dioxide cycle[J]. Advances in New and Renewable Energy, 2018, 6(1): 62-68.
PEI X Y. Economic analysis of chiller selection for central air conditioning[C]//The 12th National HVAC Technology Information Network Conference. Hangzhou, 2003: 266-271.
PARK S H, KIM J Y, YOON M K, et al. Thermodynamic and economic investigation of coal-fired power plant combined with various supercritical CO 2 Brayton power cycle[J ] . Applied Thermal Engineering, 2018, 130: 611-623.
ZHAO S F. Research about water cooling turbo chiller performance in off-design condition[J]. Refrigeration Air Conditioning&Electric Power Machinery, 2011, 32(6): 1-6.
FANG G Y, XIN L, YANG F. The developing status and trend of cool storage air-conditioning technology[J]. Refrigeration and Air-Conditioning, 2006, 6(1): 1-5.
YAO S, GU W, LU S, et al. An operational optimization method of combined cooling, heating and power system considering teat storage characteristics of buildings[J]. Distributed Energy, 2018, 3(4): 16-23.