Research on Three-phase Unbalance of Micro-grid Based on Active Disturbance Rejection Control
Energy Internet|更新时间:2025-07-04
|
Research on Three-phase Unbalance of Micro-grid Based on Active Disturbance Rejection Control
Power Generation TechnologyVol. 41, Issue 2, Pages: 160-166(2020)
作者机构:
上海电力大学自动化工程学院, 上海市 杨浦区 200090
作者简介:
基金信息:
Shanghai International Science & Technology Cooperation Program(15220710500);Shanghai Science and Technology Commission Local College Capacity Building Program(15160500800);Shanghai Science and Technology Commission Key Program(18DZ1203200)
Mengran QIAN, Hui LI, Xinxiu LIU. Research on Three-phase Unbalance of Micro-grid Based on Active Disturbance Rejection Control[J]. Power Generation Technology, 2020, 41(2): 160-166.
DOI:
Mengran QIAN, Hui LI, Xinxiu LIU. Research on Three-phase Unbalance of Micro-grid Based on Active Disturbance Rejection Control[J]. Power Generation Technology, 2020, 41(2): 160-166. DOI: 10.12096/j.2096-4528.pgt.19128.
Research on Three-phase Unbalance of Micro-grid Based on Active Disturbance Rejection Control
Under the condition of three-phase unbalanced load in micro-grid
three-phase four-leg inverter can solve the unbalanced three-phase output voltage because of unbalanced load. Nevertheless
in the
dq
0 synchronous reference frame
the output voltage and current of three-phase four-leg inverter are coupled with each other. If the load is unbalanced and the open-loop control is directly used in the
dq
0 synchronous reference frame
the output voltage is still unbalanced because of double frequency disturbance caused by unbalanced load. To solve these problems
this paper established the mathematical model of three-phase four-leg inverter
derived the open-loop transfer function of the controlled plant and deeply analyzed the mechanism of unbalanced output voltage of three-phase four-leg inverters. In addition
according to the system model information
a second-order active disturbance rejection controller (ADRC) controller was designed to decouple the voltage and current in
dq
axis
and it could reduce the number of originals measured. Proportional resonant controller was introduced to eliminate the disturbance caused by 100 Hz. Finally
the effectiveness of the solution was verified by Matlab/Simulink.