Zeng Jia-yu, Lu Yao, Cao Hao-chen, et al. Multi-dimensional Comparison and Selection of High-quality Drinking Water Renovation Project Schemes for Communities[J]. 2023, 40(3): 122-126.
Zeng Jia-yu, Lu Yao, Cao Hao-chen, et al. Multi-dimensional Comparison and Selection of High-quality Drinking Water Renovation Project Schemes for Communities[J]. 2023, 40(3): 122-126.DOI: 10.12052/gdutxb.210127.
Multi-dimensional Comparison and Selection of High-quality Drinking Water Renovation Project Schemes for Communities
In response to the "Water Pollution Prevention and Control Action Plan" promulgated by the State Council and to achieve the goal of direct drinking of municipal tap water in 2035
the secondary water supply net- work of an old community in Shanghai is simulated. According to the current pipeline network layout
three other different pipeline network layout schemes are proposed
which are simulated to compare the water age
pressure
flow rate and other hydraulic conditions at each point. Choosing a more appropriate transformation plan and comparing the current situation and planned one
the water level of the pool and the diameter of the pipe network are respectively optimized. The simulation results show that the water level optimization and pipe diameter optimization of the pool can significantly shorten the water age
and the pressure and flow velocity are in a more appropriate range. According to the simulation results
the multi-dimensional comparison and selection are finally selected based on the current situation of the optimization of the water level of the pool and the pipe diameter. After testing
all water quality indicators are up to standard after the renovation
and the residual chlorine attenuation coefficient is reduced by 53.3%.
YUAN H F, ZHAI X D, YAN X Y, et al . Examples of direct drinking water in office buildings [J ] . Shanxi Chemical Industry, 2018, 38(5): 129-131.
PANG Y W, YAN Q, REN Y Z, et al . Study on the change of water quality after secondary water supply transformation in a district of Shanghai [J ] . Water Wastewater Engineering, 2021, 57(1): 121-125.
GENG B. Estimation of water age in water pool(tank) based on water level control and suggestion for optimization [J]. Water Purification Technology, 2021, 40(5): 142-145.
LIU X Y, SHU S H, YANG K, et al . Intelligent management of secondary water supply systems in downtown Shanghai [J ] . Procedia Computer Science, 2019, 154: 206-209.
WU X, XIAO L, LIU S M, et al . Research on residual chlorine degradation in Changzhou communities [J ] . Water Wastewater Engineering, 2020, 56(10): 98-103.
王成功. 一种二次加压系统节能效果试验研究[D]. 哈尔滨: 哈尔滨工业大学, 2013.
SHAO Z, LI X, SHAO W, et al . Analysis of residual chlorine attenuation regularity for different water supply quality network [J ] . Water Technology, 2013, 7(2): 19-21.
TONG J. Study on the countermeasures of Shanghai municipal tap water to achieve the target of direct drinking [J]. Water Wastewater Engineering, 2020, 56(4): 70-75.